SRP-73

by Simex
€0,00
SKU SRP-73

Meter in small case, with current-voltage or mV input, with 1 or 2 relay (or OC type) outputs. The version without relay outputs is also available.

TECHNICAL DETAILS

Inputs

current 0-20 mA or 4-20 mA, programmable, input resistance < 65 Ohm (typ. 55 Ohm), overload-protected, input current limited to 40 mA; voltage 0-5 V, 1-5V, 0-10V or 2-10V, programmable, input resistance > 50 kOhm; milivoltage 0-60 mV, 0-75 mV, 0-100 mV, 0-150 mV; programmable; input resistance > 100 kOhm

Power consumption

for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W

Outputs

0, 1 or 2 relays 1A/250V AC (cos fi=1) or the OC 30mA/30VDC/100mW; transducer power supply output: 24V DC +5%, -10% / max. 100 mA, stabilized, not insulated from measuring inputs

Case material

NORYL- GFN2S E1

Protection class

depending on display size: for 5 x 9 mm display: IP 65 (front), available additional frame IP 65 for panel cut-out sealing; IP 20 (case and connection clips); for 4 x 13 mm display: IP 40 (front); IP 20 (case and connection clips)

Operating temperature

0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)

Display

LED, two-coloured (red-green), 4 x 13 mm (IP 40) - standard or LED, red, 5 x 9 mm (IP 65) - option

Power supply

19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC

Accuracy

± 0,25% ± one digit in the entire operation range

Measurement range

-999 ÷ 9999 + decimal point

Stability

typ. 50 ppm/°C

Communication interface

RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU (not galvanically isolated from measuring inputs)

Storage temperature

-10°C ÷ +70°C, -20°C ÷ +70°C (with option 08)

Case dimensions

72 x 36 x 97 mm

Case

panel mounting

Panel cut-out dimensions

66,5 x 32,5 mm

Installation depth

min 102 mm

 DOWNLAOD

Datasheet : SRP-73