SNA-L70 is an innovative instrument for measurement of the electrical parameters. It is particularly suitable for consumption analysis and control, with an excellent quality/price ratio.
For the version with Rogowski coils (RGW model), connections are very quick and easy, very useful for retrofitting applications on existing switchboards or for energy audit.
SNA-L70 is the ideal instrument to establish the measurement points on the plant.
The instrument can communicate through the RS-485 serial port by MODBUS RTU/ASCII protocol.
TECHNICAL DETAILS
Inputs |
Voltage range: self-powered model: 3 x 180/310 ÷ 3 x 285/495 VAC; auxiliary power supply (AUX) model: 3 x 10/17 ÷ 3 x 285/495 VAC; current: 6A (SNA-L70-111), 80A (SNA-L70-211), 3 selectable scales, 500/4000/20000A, Rogowski coils (SNA-L70-RGW); digital: active optoisolated, voltage range for DMD synchronisation: 80 ÷ 276 VAC |
Power supply |
self-powered model: 180 ÷ 285V AC, 50/60 Hz; auxiliary power supply (AUX) model: 85 ÷ 265V AC, 50/60 Hz |
Power consumption |
self-powered model: 3,5 VA ÷ 1 W for each phase; auxiliary power supply (AUX) model: 1,6 VA ÷ 1 W |
Outputs |
digital: passive optoisolated; self-powered model: 250 VAC/DC - 100 mA; auxiliary power supply (AUX) model: 27 VDC - 27 mA |
Protection class |
IP 51 (frontal part), IP 20 (terminals) |
Operating temperature |
-25°C ÷ +55°C |
Display |
backlighted LCD, 3 rows, 4 digits + symbols |
Weight |
max. 436 g |
Communication interface |
RS-485 optoisolated, Modbus RTU/ASCII |
Accuracy |
voltage: ±0,2% reading in 10% FS...FS range; current: ±0,4% reading in 5% FS...FS range; power: ±0,5% reading ±0,1% FS (PF=1); frequency: ±0,1% reading ±1 digit in 45...65 Hz range; active energy: Class 1 according to IEC/EN 62053-21; reactive energy: Class 2 according to IEC/EN 62053-23 |
Storage temperature |
-25°C ÷ +75°C |
Case dimensions |
72 x 90 x 65 mm |
Case |
DIN TS-35 mounting |
Relative humidity |
80% max without condensation |