Use the pressure probe to determine differential pressures and flow velocities (in combination with a Pitot tube). Both Prandtl Pitot tubes (Ø 7 mm) and straight Pitot tubes (Ø 8 mm) can be used for flow measurement.
Pressure plays an important role as a measurement parameter, particularly in power and air conditioning technology, as well as in industrial process technology. The difference between the static pressures is measured in the course of acceptance test measurements to check the pressure drop of built-in components (e.g. air filters).
TECHNICAL DETAILS
Differential Pressure - Piezoresistive |
|
Measuring range |
0 to +100 hPa |
Accuracy |
±0.1 hPa (+1 to +20 hPa) ±0.5 % of mv (+20 to +100 hPa) |
Overload |
200 hPa |
General technical data |
|
Operating temperature |
0 to +50 °C |
Cable length |
1.5 m |
Storage temperature |
-20 to +70 °C |